The ACB E2.2N is a 2000A, 4P, withdrawable circuit breaker with a rating of 66kA. It has an In (rated current) of 2000A and offers different current ranges for different functions: L-I1 (long-time delay) ranges from 800-2000A, S-I2 (short-time delay) ranges from 1200-20000A, I-I3 (instantaneous trip) ranges from 3000-30000A, and G-I4 (ground fault protection) ranges from 200-2000A. This circuit breaker features an auto EKIP Touch LSIG trip unit and HR-HR terminals. It also comes complete with WMP+FP functionality.

Technical Specifications

Brand ABB
AC Voltage (V) 690
Breaking Capacity (kA) 66 @415V AC
Breaking Capacity 415V AC - Icu (kA) 66
Component Type Withdrawable
Current Rating (A) 2000
Frame E2.2
G (0.1 to 1 x In) - I4 (A) 200-2000
I (1.5 to 15 x In) - I3 (A) 3000-30000
Icw (kA/1s) - Short-time Withstand Current Rating 66
Iu - Uninterrupted Current Rating (A) 2000
L (0.4 to 1 x In) - I1 (A) 800-2000
No. of Poles 4P
Poles 4P
Power Loss (W) 450
Rated Current (A) 2000
Rated Impulse Withstand Voltage (kV) 12
Rated Insulation Voltage AC (V) 1000
Rated Operational Voltage AC (V) 690
Rated Short-time Withstand Current - Icw (kA/1s) 66
Rated Uninterrupted Current - Iu (A) 2000
S (0.6 to 10 x In) - I2 (A) 1200-20000
Size of Frame E2.2
Standards and Approvals IEC
Terminal Type HR-HR
Trip Unit EKIP Touch LSIG
Trip Unit - Electronic EKIP Touch LSIG
Version Withdrawable