Products

ABB DSE203NC10A30 Residual Current ACB 6kA 3P+N-P 30mA 10A C-Curve TypeA Chassis Mounting IP20

Product Code: DSE203NC10A30

  • 3P+N RCBO with Type A residual current
  • Rated voltage of 400/415 VAC
  • Short circuit capacity of 6 kA
  • Compact size: 53.4 mm width
  • Complies with IEC and AS/NZS standards
In Stock Low Stock Out Of Stock Please See Attributes

Specifications

Product Type Residual Current Circuit Breaker with Overcurrent Protection
Brand ABB
Series DSE203N
Ambient Temperature -5 to 55 deg C
Cable Cross Section 1-25 sq-mm 1-Solid-Core, 1-16 sq-mm 4-Multi-Wired
Connecting Capacity Busbar 10 sq-mm, Rigid 1-25 sq-mm, Flexible 1-16 sq-mm
Curve Type C
Degree of Pollution IP2
Degree of Protection IP20
Depth 71.6 mm
Earthing Switch Type Undelayed
Electrical Durability 10000 Cycles
Height 117.5 mm
Mounting Type Chassis
Number of Poles 3P+N
Operating Characteristic Instantaneous
Overvoltage Category III
Power Loss 5.74 W
Power Supply Connection Bottom
Rated Current 10 A
Rated Frequency 50/60 Hz
Rated Impulse Withstand Voltage 4 kV
Rated Insulation Voltage 500 V
Rated Short Circuit Current 30 mA
Rated Voltage 400/415 VAC
Residual Current Type Type A
Short Circuit Capacity 6 kA
Standards and Approvals IEC 61009-1, IEC 61009-2-2, AS/NZS 61009-1
Weight 0.549 kg
Width 53.4 mm

Description

<p>The RCBO is a robust and reliable device designed to ensure safety and efficiency in both industrial and commercial electrical systems. With its Rated Current of 10 A, it provides optimal protection against overloads and short circuits, making it a critical component in safeguarding electrical installations.</p><p>This RCBO operates at a Rated Voltage of 400/415 VAC, suitable for standard Australian power networks. Its Rated Insulation Voltage stands at 500 V with an impressive Rated Impulse Withstand Voltage of 4 kV, ensuring resilience against voltage spikes. The product adheres to stringent Standards and Approvals including IEC 61009-1, IEC 61009-2-2, and AS/NZS 61009-1, ensuring compliance with international quality benchmarks.</p><p>Designed for durability, this RCBO boasts an Electrical Durability of up to 10,000 cycles. It features a Short Circuit Capacity of 6 kA which ensures dependable performance during fault conditions. The unit’s Residual Current Type A provides effective protection against earth faults by detecting both AC and pulsating DC residual currents.</p><p>The device&amp;#39;s physical dimensions are compact yet substantial enough for sturdy installation: Width is 53.4 mm, Height is 117.5 mm, and Depth measures at 71.6 mm with a Weight of just over half a kilogram (0.549 kg). This makes it easy to integrate into existing setups without requiring extensive space adjustments.</p><p>For versatility in different environments, the RCBO offers a Degree of Protection rated at IP20 with additional Degree of Pollution marked as IP2—ideal for indoor settings where dust ingress must be minimized but water resistance isn&amp;#39;t paramount. It supports operating temperatures ranging from -5 to +55&amp;#176;C which accommodates most climate conditions found across Australia.</p><p>Installation flexibility is enhanced by the product’s Mounting Type on chassis configurations while its Power Supply Connection from the bottom allows streamlined wiring practices often preferred by electricians working within tight spaces or complex panel arrangements.</p><p>With connecting capacities that include Busbar connections up to 10 sq-mm as well as Rigid cables between 1–25 sq-mm or Flexible cables from 1–16 sq-mm; this unit caters well to various cabling requirements typical in diverse applications—from small-scale setups needing solid-core conductors through larger multi-wired configurations demanding higher connectivity standards.</p><p>Safety considerations are further addressed via Overvoltage Category III classification—providing extra assurance when dealing with transient voltages typically encountered within industrial settings—and an Earthing Switch Type classified as Undelayed which facilitates instantaneous operational characteristics vital for quick response scenarios under fault conditions such as those necessitating immediate disconnection upon detection anomalies like ground faults or leakage currents surpassing set thresholds (Rated Short Circuit Current being specified at sensitive levels like only reaching up till thirty milliamperes).</p><p>Overall this RCBO exemplifies reliability engineered into every facet—from technical specifications meeting rigorous industry guidelines down towards practical usability factors aligning perfectly alongside everyday operational demands faced routinely by professionals across varied sectors reliant heavily upon uninterrupted power continuity coupled alongside uncompromising safety assurances inherent throughout deployment phases involved therein!</p>

Documents

  • IPD Product Catalogue

    IPD Product Catalogue V17
Products to compare: