Products

ABB 1SDA067036R1 Moulded Case Circuit Breaker 690/500VAC/VDC 50A 4-P 36kA TMA 300-500A Front For: XT2N

Product Code: 1SDA067036R1

  • MCCB with 50 A rated current
  • 36 kA breaking capacity
  • Front connection, bolt terminals
  • IP20 protection, IEC60947-2 compliant
  • Suitable for XT2N applications
In Stock Low Stock Out Of Stock Please See Attributes

Specifications

Product Type Moulded Case Circuit Breaker
Brand ABB
Breaking Capacity 36 kA
Connection Type Front
Current Setting Range 35-50 A
Degree of Protection IP20
Main Circuit Connecting Capacity 32.5-100 sq-mm
Number of Poles 4
Power Loss 4.09 W
Rated Current 50 A
Rated Frequency 50/60 Hz
Rated Impulse Withstand Voltage 8 kV
Rated Insulation Voltage 1000 V
Rated Short Circuit Current 300-500 A
Rated Voltage 690/500 VAC/VDC
Release Type TM
Standards and Approvals IEC60947-2
Suitable For Use With XT2N
Terminal Type Bolt
Trip Unit TMA
Weight 1.45 kg
Width 120 mm

Description

<p>When it comes to selecting a reliable and efficient Molded Case Circuit Breaker (MCCB) for industrial and commercial applications, this model stands out with its robust specifications. Designed to meet the demands of modern electrical systems, it offers a balance of performance and protection.</p><p>At the core of its functionality is the rated current of 50 A, making it suitable for a variety of medium-load applications. The MCCB operates effectively within a rated voltage range of 690 VAC or 500 VDC, providing versatility across different power systems. Its rated impulse withstand voltage is an impressive 8 kV, ensuring resilience against transient overvoltages typically encountered in industrial settings.</p><p>Safety and reliability are paramount, and this MCCB doesn&amp;#39;t disappoint with its IP20 degree of protection. This rating ensures that users are shielded from accidental contact with live parts while preventing ingress by objects larger than 12 mm. The breaker also adheres to IEC60947-2 standards, underscoring its quality and compliance with international safety requirements.</p><p>The trip unit features a Thermal Magnetic (TM) release type with an adjustable current setting range from 35 to 50 A, allowing for tailored protection based on specific circuit needs. It boasts a breaking capacity of 36 kA at maximum fault conditions—providing peace of mind knowing that your system is safeguarded against potential short circuits.</p><p>Its design includes four poles for balanced load distribution across phases in three-phase systems or additional configurations as needed. Connection is straightforward via front bolt terminals that accommodate main circuit connecting capacities ranging from 32.5 to 100 square millimeters—offering flexibility in installation setups.</p><p>Weighing in at just 1.45 kg and measuring a compact width of 120 mm, this MCCB integrates easily into existing panels without demanding significant space adjustments. Operating efficiently within a frequency range of both 50 Hz and 60 Hz further enhances its adaptability across various regions.</p><p>Power loss is minimized at only 4.09 W under normal operating conditions—contributing not only to energy efficiency but also reducing thermal stress on surrounding components over time.</p><p>This MCCB pairs seamlessly with XT2N systems, expanding compatibility options for those seeking integration into broader network architectures or expansions thereof.</p><p>In summary, this MCCB delivers dependable performance backed by stringent safety standards—it’s engineered for those who prioritize technical precision alongside operational dependability in their electrical infrastructure solutions.</p>